Stair rules in England: rise, going, pitch and headroom

Approved Document K sets the steps of a stair in England by how the stair is used. A stair inside a house follows the private stair row. This guide lists the figures, the headroom, tapered treads and handrails, and says where a drawing office checks them.

Stair rules in England: rise, going, pitch and headroom

Three stair categories

Table 1.1 of Approved Document K (2013 edition) gives rise and going limits for three categories. A private stair is one used by a single dwelling. A utility stair is used for escape, access for maintenance or other purposes that are not the usual route between levels. A general access stair serves all users of a building on a day-to-day basis.

The category matters because the limits are quite different. A private stair can be steeper than a general access stair, so a stair that works in a house will not necessarily work in an office or a block of flats. Say which one you need before we draw anything.

Rise and going, Approved Document K Table 1.1 (mm)
Stair categoryRiseGoingNotes
Private stair150-220220-300Maximum pitch 42 degrees
Utility stair150-190250-400Escape, maintenance access
General access stair150-170250-400Day-to-day use by all
All categories2R + G550-700Normal relationship

Swipe the table sideways to see every column.

Rise, going and pitch

For a private stair, the rise is 150 mm to 220 mm, the going is 220 mm to 300 mm, and the pitch must not exceed 42 degrees. A utility stair has a rise of 150 mm to 190 mm and a going of 250 mm to 400 mm. A general access stair has a rise of 150 mm to 170 mm and a going of 250 mm to 400 mm.

The document says the normal relationship between the two is that twice the rise plus the going equals between 550 mm and 700 mm. A 170 mm rise with a 250 mm going gives 590 mm and sits inside the band. Any rise within its range may be used with any going within its range, provided the relevant note in the table is met.

In a flight, all the steps use the rise and going limits of the same category (paragraph 1.3). We check the whole flight on the model and report the total rise, the number of risers, the going, the pitch and the 2R+G value for each. The total height between floors rarely divides into a perfect rise, so we adjust the number of risers to bring it into range.

Headroom

Paragraph 1.11 asks for the minimum headroom shown in Diagram 1.3, which is at least 2 m vertically above the pitch line of the flight and above the landings. It applies to all buildings. Loft conversions have a reduced headroom allowance in Diagram 1.4, but only where there is no room to meet the full figure.

Where the soffit under a stair is less than 2 m above floor level, paragraph 1.8 asks for guarding and low-level cane detection, or a barrier giving the same protection. This matters in open-plan houses where the stair stands in a room.

Open risers, tapered treads and spirals

In dwellings, steps with open risers must overlap the treads by at least 16 mm and a 100 mm sphere must not pass through the gap (paragraph 1.9). In buildings other than dwellings, risers must not be open.

Tapered treads are measured to Diagram 1.9. Where the stair is 1 m wide or more, the going is taken 270 mm in from each side. Where it is narrower than 1 m it is taken at the centre. The narrow end of a tread must be at least 50 mm wide. Consecutive tapered treads must have the same going (paragraph 1.26). For dwellings, external tapered steps that are part of the building need a going of at least 280 mm at each step.

Spiral and helical stairs are designed to BS 5395-2 (paragraph 1.28), a standard we do not reproduce here.

Handrails and guarding on the stair

The top of the handrail sits 900 mm to 1000 mm above the pitch line or floor, and a stair 1000 mm or wider needs a handrail on both sides (paragraph 1.34). In a dwelling, guarding is needed at the sides of flights and landings where the drop is more than 600 mm (paragraph 1.41). A circular handrail is 32 mm to 50 mm in diameter (Diagram 1.13).

On a steel stair we draw the handrail as one straight run on the pitch, with posts set out from the nosings. Where the handrail finishes at a landing, we show its height against the landing guard so that the join is clear before the metal is cut.

What the drawings check

We check the dimensions on the model, report them and show them on the drawing: total rise, number of risers, rise, going, 2R+G, pitch, headroom, handrail height and the 100 mm sphere. If the numbers fail, we say which one and by how much. Your engineer designs the steel and the fixings, and building control gives the final word on whether the stair complies.

Existing buildings are handled differently. The document says Table 1.1 should be followed unless dimensional constraints make that not possible, and any alternative should be agreed with the building control body. Tell us what the constraint is.

Questions

What is the maximum rise for a stair in a house?

220 mm for a private stair, with a going of 220 mm to 300 mm and a pitch of no more than 42 degrees (Approved Document K, Table 1.1).

What is the headroom on a stair?

At least 2 m above the pitch line and landings (Approved Document K, paragraph 1.11 and Diagram 1.3). Loft conversions have a reduced allowance only where the full figure cannot be met.

What is the 2R+G rule?

Twice the rise plus the going should be between 550 mm and 700 mm. It checks that the steps feel comfortable together.

Can open-riser stairs be used?

In dwellings, yes, if the treads overlap by at least 16 mm and a 100 mm sphere cannot pass. In buildings other than dwellings the risers must not be open.

How wide does a stair need to be?

For flights in buildings other than dwellings, paragraph 1.15 asks for 1200 mm between enclosing walls or strings. A stair 1000 mm or wider needs a handrail on both sides. Ask your building control body about a house.

Do the rules apply to Scotland and Wales?

This guide covers England. Wales and Scotland use their own documents. Check with building control.

Sources

Read on the published page. These guides are for England unless they say otherwise, and explain the documents: your council, building control body and engineer decide your job.

  1. Approved Document K: Protection from falling, collision and impact, 2013 edition (England), Table 1.1, p.5“twice the rise plus the going (2R + G) equals between 550mm and 700mm”
  2. Approved Document K: Protection from falling, collision and impact, 2013 edition (England), Table 1.1 note 1, p.5“The maximum pitch for a private stair”
  3. Approved Document K: Protection from falling, collision and impact, 2013 edition (England), para 1.11“provide the minimum headroom shown in Diagram 1.3”
  4. Approved Document K: Protection from falling, collision and impact, 2013 edition (England), para 1.9“Overlap treads by a minimum of 16mm”
  5. Approved Document K: Protection from falling, collision and impact, 2013 edition (England), para 1.34a, p.14“the top of the handrail 900mm to 1000mm from the pitch line”