Copings, cills, cappings, fascias and soffits, rainscreen cassettes, flashings and window surrounds: every length drawn flat, with its folds, its holes and a DXF for the folder.

Folded aluminium, rendered from a 3D model

Side by side

Cost bands are our own view of relative price for a typical job, not quotes: £ is the cheapest to draw and make, £££ the dearest.

TypeSits onSheet we drawWhat the drawing settlesCost band
CopingsTop of a masonry or concrete wall2 mm to 450 mm wide, 3 mm overFall, overhang, drip, strap and joint gaps£
Pressed cillsUnder a window or door opening2 mmProjection, fall, drip, stop ends, clip positions£
CappingsSteel edges, balcony frames, upstands2 mm, 3 mm if curved and weldedFall, hooked drip, facets, strap slots££
Fascias and soffitsBalcony and canopy edges and undersides2 mmPlank joints, carriers, falls to the drip££
Rainscreen cassettesFacades, on rails2 or 3 mmPanel size and stiffeners against a tested line, joints£££
Flashings and surroundsJunctions and window reveals1.6 mmLaps, direction of lap, brackets, reveal fit£
Roof cowlsAn upstand round a riser opening on a flat roof2 mm EN AW-5005, powder coatedCapping fall, the overhang over the cut-out, drips, closers, board and membrane££

Swipe the table sideways to see every column.

How to choose

Folded aluminium is made flat and folded on a press brake, so every piece is drawn as its flat pattern: the blank, the folds up and down, the holes, and the corner fittings mitred or welded.

Every fold is checked against what a press brake can do with that alloy and thickness before the sheet is issued.

Start from where the metal goes. Metal that covers the top of something is a coping or a capping: a coping on a masonry wall, a capping on a steel edge or balcony frame. Metal under an opening is a cill, around it is a surround, and at a junction between materials it is a flashing. Metal along a balcony edge and underneath it is a fascia and soffit, and metal that makes the face of a wall is a cassette. If your job has several of these, they should be drawn together, because the joints between them are where leaks and gaps appear.

Price is set by the number of different parts more than by the metres of aluminium. A long plain run of one profile is cheap to make. Every corner, apex, step, end cap and change of width becomes a fitting that is mitred and welded or folded as its own piece, and each one needs its own flat pattern and DXF. A balcony with curved edges, stubs and columns will have many unique parts. Gauge matters next: wide parts need 3 mm sheet where narrow ones use 2 mm, and welded curves are made in 3 mm. Sheet comes in stock sizes, so a part wider than the sheet's width wastes material or needs a joint, and press brakes fold to about 3 m as standard.

To get a pack drawn, send the elevations and sections you have, the wall build-up behind the metal, the colour, and photographs of every corner and junction. For anything on a tall residential block tell us the height at the start, because the fire rules for external walls and balconies change what the metal is fixed to and what has to be evidenced. We check every fold against what a press brake can do with that alloy and gauge, and every fixing against the expansion the metal will see, before a sheet is issued.

What the drawings show

  • A run plan with every length and fitting marked
  • An A4 sheet per length: profile, flat pattern, folds and holes
  • DXFs on layers CUT, HOLES, BEND-UP, BEND-DOWN and ETCH-TEXT
  • Schedules, bought-in lists and fixings

Questions

What fall does a parapet coping need?

LABC Warranty asks for a minimum fall of 2 degrees from horizontal on the top surface, an overhang of at least 40 mm each side of the wall below and a throating or drip.

What fall should a window cill have?

Makers of metal cills ask for a minimum fall of 5 or 8 degrees after installation. We draw 5 degrees on the standard pressed cill and 8 degrees on cappings.

Do rainscreen panels need fire evidence?

On relevant residential buildings with a storey at least 18 m up, every material in the external wall must be Euroclass A2-s1, d0 or A1: the sheet, rails, fixings and finish all need evidence. We state the class assumed on the drawing.

Send the drawings.

Send the drawings and get a fixed price back within 4 working hours (Mon-Fri, 8 am-6 pm).

Not ready to send drawings? Ask for the full sample pack for your type of work, or a call back, with the form.

Big files: paste a WeTransfer, Dropbox or Google Drive link, or send them when we reply.